功率200KW以上原装进口康明斯发电机组型号参数综合列表
信息来源:www.sgfdj.com 发布日期:2020-08-24 浏览次数:
机组型号
|
10LAG2
|
10LAG3
|
8TAG2
|
8TAG4
|
19TAG2
|
19TAG3
|
19TAG4
|
28TAG5
|
30QSTG1
|
30QSTG2
|
38TAG1
|
38TAG2
|
38TAG3
|
38TAG5
|
50TAG1
|
50TAG3
|
50TAG8-1
|
50TAG8-2
|
||
频率
|
50HZ
|
|||||||||||||||||||
转速
|
1500rpm
|
|||||||||||||||||||
功能
|
备用/主用
|
|||||||||||||||||||
额定功率KW(千瓦)
|
220/180
|
220/200
|
275/250
|
310/282
|
330/300
|
400/360
|
440/400
|
550/500
|
620/560
|
705/630
|
620/560
|
660/600
|
800/725
|
880/800
|
880/800
|
1100/1000
|
1200/1100
|
1290/1100
|
||
载荷平均油耗
|
25%
|
16.6/15.1
|
16.6/15.1
|
24/22
|
23/21
|
32/29
|
33/30
|
35/32
|
48/44
|
/44
|
/48
|
57/52
|
58/53
|
70/64
|
71/65
|
80/73
|
90/82
|
90/82
|
93/85
|
|
50%
|
28.7/26.1
|
29.7/26.9
|
41/37
|
43/39
|
51/46
|
56/51
|
63/57
|
80/73
|
/78
|
/87
|
96/87
|
99/90
|
118/107
|
124/113
|
132/120
|
152/138
|
152/138
|
164/149
|
||
75%
|
40.8/37.1
|
43.0/39.0
|
58/53
|
63/57
|
70/64
|
80/73
|
91/83
|
116/105
|
/116
|
/128
|
135/123
|
141/128
|
165/150
|
177/161
|
185/168
|
215/195
|
215/195
|
234/213
|
||
100%
|
53.4/48.4
|
55.6/51.1
|
78/70
|
84/76
|
91/83
|
109/97
|
123/109
|
156/140
|
169/153
|
187/168
|
176/160
|
184/167
|
215/194
|
228/209
|
237/217
|
282/254
|
305/254
|
321/274
|
||
柴油机型号
|
LTA10G2
|
LTA10G3
|
NTA855G2
|
NTA855G4
|
KTA19G2
|
KTA19G3
|
KTA19G4
|
VTA28G5
|
QST30G1
|
QST30G2
|
KTA38G1
|
KTA38G2
|
KTA38G3
|
KTA38G5
|
KTA50G1
|
KTA50G3
|
KTA50G8
|
KTA50G8
|
||
冲程
|
4
|
|||||||||||||||||||
气缸
|
6
|
12
|
16
|
|||||||||||||||||
吸气
|
涡轮增压及增压冷却
|
涡轮增压及低温后冷却
|
||||||||||||||||||
调速器类型
|
EFC(调速器)
|
直接注射(电子式)
|
EFC(调速器)
|
PT泵直接喷射(电子式)
|
||||||||||||||||
缸径与冲程
|
125*136
|
125*136
|
140*152
|
140*152
|
159*159
|
140*152
|
140*165
|
159*159
|
||||||||||||
汽缸容量
|
10
|
10
|
14
|
14
|
19
|
28
|
30.48
|
38
|
50
|
50.3
|
||||||||||
滑油系统总容量
|
36
|
36
|
38.6
|
38.6
|
50
|
83
|
154
|
135
|
177
|
204
|
||||||||||
最大滑油耗(升/时)
|
0.24
|
0.24
|
0.24
|
0.24
|
0.31
|
0.5
|
0.62
|
0.71
|
||||||||||||
总功率(KW/BHP)
|
231/310
|
246/330
|
321/430
|
351/470
|
369/495
|
448/600
|
504/675
|
612/810
|
768/1030
|
768/1030
|
701/940
|
731/980
|
895/1200
|
970/1300
|
970/1300
|
1195/1600
|
1320/1770
|
1402/1880
|
||
压缩比
|
16.0:1
|
16.0:1
|
14.0:1
|
14.0:1
|
14.5:1
|
13.9:1
|
13.9:1
|
13.1:1
|
14.0:1
|
14.0:1
|
14.5:1
|
14.5:1
|
13.9:1
|
13.9:1
|
14.5:1
|
13.9:1
|
14.9:1
|
14.9:1
|
||
冷却系统散热(kWm)
|
120/108
|
128/116
|
189/167
|
206/187
|
226/206
|
274/247
|
308/274
|
375/340
|
377/326
|
424/382
|
429/388
|
496/407
|
548/493
|
594/539
|
617/560
|
723/646
|
616/545
|
616/545
|
||
冷却水箱散热量
|
209/280
|
224/300
|
283/380
|
317/425
|
336/450
|
403/540
|
448/600
|
556/745
|
634/850
|
689/935
|
634/850
|
664/890
|
806/1080
|
880/1180
|
880/1180
|
1080/1447
|
1180/1590
|
1182/1585
|
||
室内热辐射(kWm)
|
32/29
|
34/31
|
47/42
|
51/46
|
55/50
|
64/58
|
74/66
|
94/85
|
102/93
|
112/101
|
106/97
|
123/101
|
130/117
|
137/125
|
153/131
|
170/153
|
184/160
|
193/166
|
||
散热器冷却剂容量(升)
|
48
|
49
|
64
|
64
|
91
|
91
|
91
|
167
|
195
|
195
|
308
|
323
|
323
|
323
|
348
|
358
|
358
|
358
|
||
冷却剂流量(升/分)
|
280
|
280
|
390
|
390
|
594
|
594
|
731
|
731
|
720
|
720
|
1298
|
1298
|
1287
|
1173
|
2078
|
1730
|
1730
|
1730
|
||
最大冷却剂损耗压差(KPA)
|
41
|
41
|
41
|
41
|
55
|
55
|
55
|
55
|
48
|
48
|
48
|
48
|
48
|
48
|
69
|
69
|
70
|
70
|
||
最大冷却剂静压(M)
|
18.3
|
18.3
|
18.3
|
18.3
|
18.3
|
18.3
|
18.3
|
14
|
14
|
18.3
|
18.3
|
18.3
|
18.3
|
18.3
|
18.3
|
16.3
|
18.3
|
|
||
散热风扇载荷(KW)
|
8.5
|
4..8
|
7.4
|
7.4
|
5
|
5
|
5.2
|
22.4
|
18.4
|
17.9
|
17.9
|
17.9
|
17.9
|
24.6
|
24.6
|
24.6
|
24.6
|
|||
助燃空气(立方/分)
|
15.0/14.2
|
15.0/14.2
|
23.9/20.7
|
23.9/20.7
|
26.8/26.8
|
34.5/34.5
|
34/30.9
|
52.4/49.0
|
51.2/50.1
|
50.3/50.3
|
53.0/49.6
|
64.0/60.0
|
73.5/69.1
|
70.9/66.6
|
98.6/92.7
|
98.6/92.7
|
98.6/92.7
|
|||
散热器冷却空气(立方/分)
|
314
|
314
|
351
|
351
|
518
|
518
|
518
|
1246
|
1120
|
1003/1003
|
864
|
864
|
1362
|
1558
|
1558
|
1558
|
1558
|
|||
蓄电(KW)
|
19
|
19
|
33
|
33
|
57
|
57
|
57
|
70
|
100
|
110
|
110
|
110
|
110
|
140
|
140
|
140
|
140
|
|||
输出电压选择(12导线换接)
|
50HZ/3相专用电压/可换接
|
|||||||||||||||||||
110/190V,115/200V,120/208V,110/220V
|
||||||||||||||||||||
220/380V,230/400V,240/416V
|
||||||||||||||||||||
发电机组尺寸(mm)
|
长
|
3000
|
3000
|
3000
|
3000
|
3505
|
3505
|
3505
|
4000
|
4570
|
4630
|
4630
|
4630
|
4630
|
5850
|
5850
|
5850
|
5540
|
||
宽
|
1055
|
1055
|
1055
|
1055
|
1245
|
1245
|
1245
|
1448
|
1780
|
1905
|
1905
|
1905
|
1905
|
1905
|
1905
|
1905
|
1905
|
|||
高
|
1625
|
1625
|
1625
|
1625
|
1727
|
1727
|
1727
|
2057
|
2218
|
2540
|
2540
|
2540
|
2540
|
2540
|
2540
|
2540
|
2540
|
|||
重量(KG)
|
2651
|
2651
|
2747
|
2747
|
3575
|
3668
|
3668
|
5766
|
7416
|
7872
|
7416
|
7872
|
8149
|
9116
|
9116
|
10016
|
10016
|
10020
|
||
交流发电机:发电机类型为无刷,自励磁,自散热,有屏蔽保护IP21,单级轴承,4级,防滴漏结构,超额工况下温升不超过125摄氏度。其电压可谓幅度为+/-10%。绝缘为H级,符合HEMA,IEC,IEEE,CSA及BS要求,稳定从空载到满载在0.25%内电压波动范围;加载后,从空载到满载不超过平均值+/-0.5%。频率调节:从空载到满载的各种负载情况下,不超过平均值的+/-0.25%。交流阶波波动总量:从空载到满载,波动总量不超过5%,单个节波不超过3%,电话影响系数:按NEMA需求<50,定子:斜定子,2/3间距绕组,减少磁场发热及电压波动。波动发电机能承受过载3倍额定电流历时10秒。
|
康明斯电力发电机组容量在200Kw以上采用康明斯公司设计制造之专用电子调速器,其优越之性能,提供发电机组在额定容量内均能保持50Hz同步运转。康明斯电力发电机组采用引以为傲的P.M.G激磁系统,机组可以承受额定容量100%一次投载而不致影响机组运转及输出。康明斯发电机组容量在200Kw以上,均采用永久磁铁激磁式发电机。在加/卸载时,其电压回覆时间较他种发电机更为快速。容量在200Kw以下亦可选用永久磁铁激磁式发电机。
康明斯电力发电机组且容量在200Kw以上,发电机组引擎采用康明斯公司专利制造之P.T低城市燃油系统,不论引擎汽缸容量大小,只采用单一燃油供应管路,且在燃油系统中,如有空气渗入时,不致导致引擎失去动力而停车。由于独特之燃油系统设计机组,有绝佳的启动能力,并能在10秒内达到稳定输出。
------------
展望未来
■ 三款大马力柴油机平台将导入中国本地化生产
■ 计划新建大马力制造基地和研发中心
■ 大力进军柴油发电机组租赁领域
■ 引进先进的50-72升排量全电控柴油机平台
■ 进一步提升康明斯在中国的产能与实力
质量方针
■ 以最低的成本及时向用户提供产品和服务
■ 始终如一地满足或超出客户提出的标准和要求
获取资讯
■ 了解更多柴油机产品动态和资讯,请关注康明斯官网
■ 官方互联网发布渠道:https://www.sgfdj.com